REPAIR WORKS OF A LEAKING 3MVA 88KV TRANSFORMER AT NCEMA PUMP STATION

Project Name:
REPAIR WORKS OF A LEAKING 3MVA 88KV TRANSFORMER AT NCEMA PUMP STATION
Description:

REPAIR WORKS OF A LEAKING 3MVA 88KV TRANSFORMER AT NCEMA PUMP

Line Item Details
Item No. UNSPSC Lot Name Lot Description Quantity Unit of Measure
1 39121706 Transformer bushings Collect oil samples before service and after service for testing x 2 Transformers 2 Lump Sum
2 39121706 Transformer bushings Disconnect LT cables x 2 Transformers 2 Lump Sum
3 39121706 Transformer bushings Disconnect HT cables x 2 Transformers 2 Lump Sum
4 39121706 Transformer bushings Disconnect tertiary transformer feeder cables 2 Lump Sum
5 39121706 Transformer bushings Replace gaskets and cone seals on LT bushings on both HV transformer and tertiary transformer 2 Lump Sum
6 39121706 Transformer bushings Replace gaskets and cone seals on HT bushings on both HV transformer and tertiary transformer 2 Lump Sum
7 39121706 Transformer bushings Replace HV bushings with new ones x 1 transformer 3 Each
8 39121706 Transformer bushings Terminate 6.6kV LV cable x 2 Transformers 2 Lump Sum
9 39121706 Transformer bushings Terminate tertiary transformer feeder cable x 2 Transformers 2 Lump Sum
10 39121706 Transformer bushings Re tighten all connections feeding and outgoing from the transformer x 2 Transformers 2 Lump Sum
11 39121706 Transformer bushings Properly mount all external mechanical support structures, e.g. structures supporting bushings and cables x 2 Transformers 2 Lump Sum
12 39121706 Transformer bushings Change silica gel x 2 Transformers 2 Lump Sum
13 39121706 Transformer bushings Perform surge arrestor tests- ground terminal to ground and visual mechanical damage inspection x 2 Transformers 2 Lump Sum
14 39121706 Transformer bushings Change membrane on pressure release valves and carry out visual mechanical damage tests x 2 Transformers 2 Lump Sum
15 39121706 Transformer bushings Connect LT cables x 2 Transformers 2 Lump Sum
16 39121706 Transformer bushings Connect HT cables x 2 Transformers 2 Lump Sum
17 39121706 Transformer bushings Regenerate transformer oil both on 3MVA transformer and tertiary transformer x 2 Transformers 2 Lump Sum
18 39121706 Transformer bushings Change or fill up mercury in bulchoz relay (where necessary) and perform dry air tests x 2 Transformers 2 Lump Sum
19 39121706 Transformer bushings Test 3MVA transformer to ZETDC standards – to be done by ZETDC x 2 Transformers 2 Lump Sum
20 39121706 Transformer bushings Test tertiary transformer to ZETDC standards – to be done by ZETDC x 2 Transformers 2 Lump Sum
21 39121706 Transformer bushings Clean transformers externally, clean the substation and supply weed killer. x 2 Transformers 2 Lump Sum
22 39121706 Transformer bushings Paint the transformers x 2 Transformers 2 Lump Sum
23 39121706 Transformer bushings Commission the transformers x 2 Transformers 2 Lump Sum
  -