NCEMA PUMP STATION
Electrical Products: Cables and Materials, Power Back-Up Equipment, Transformers, Standby Generators, Consumables & Accessories,Installation, Repair & Maintenance of Electrical Equipment, Generators, Power Back-Up Equipment & Miscellaneous Electrical Repair Works
7 Day(s)
CITY OF BULAWAYO
02-Oct-2025 02:51 PM
REPAIR WORKS OF A LEAKING 3MVA 88KV TRANSFORMER AT NCEMA PUMP STATION
Project Name: REPAIR WORKS OF A LEAKING 3MVA 88KV TRANSFORMER AT NCEMA PUMP STATION |
Description: REPAIR WORKS OF A LEAKING 3MVA 88KV TRANSFORMER AT NCEMA PUMP |
Item No. | UNSPSC | Lot Name | Lot Description | Quantity | Unit of Measure |
---|---|---|---|---|---|
1 | 39121706 | Transformer bushings | Collect oil samples before service and after service for testing x 2 Transformers | 2 | Lump Sum |
2 | 39121706 | Transformer bushings | Disconnect LT cables x 2 Transformers | 2 | Lump Sum |
3 | 39121706 | Transformer bushings | Disconnect HT cables x 2 Transformers | 2 | Lump Sum |
4 | 39121706 | Transformer bushings | Disconnect tertiary transformer feeder cables | 2 | Lump Sum |
5 | 39121706 | Transformer bushings | Replace gaskets and cone seals on LT bushings on both HV transformer and tertiary transformer | 2 | Lump Sum |
6 | 39121706 | Transformer bushings | Replace gaskets and cone seals on HT bushings on both HV transformer and tertiary transformer | 2 | Lump Sum |
7 | 39121706 | Transformer bushings | Replace HV bushings with new ones x 1 transformer | 3 | Each |
8 | 39121706 | Transformer bushings | Terminate 6.6kV LV cable x 2 Transformers | 2 | Lump Sum |
9 | 39121706 | Transformer bushings | Terminate tertiary transformer feeder cable x 2 Transformers | 2 | Lump Sum |
10 | 39121706 | Transformer bushings | Re tighten all connections feeding and outgoing from the transformer x 2 Transformers | 2 | Lump Sum |
11 | 39121706 | Transformer bushings | Properly mount all external mechanical support structures, e.g. structures supporting bushings and cables x 2 Transformers | 2 | Lump Sum |
12 | 39121706 | Transformer bushings | Change silica gel x 2 Transformers | 2 | Lump Sum |
13 | 39121706 | Transformer bushings | Perform surge arrestor tests- ground terminal to ground and visual mechanical damage inspection x 2 Transformers | 2 | Lump Sum |
14 | 39121706 | Transformer bushings | Change membrane on pressure release valves and carry out visual mechanical damage tests x 2 Transformers | 2 | Lump Sum |
15 | 39121706 | Transformer bushings | Connect LT cables x 2 Transformers | 2 | Lump Sum |
16 | 39121706 | Transformer bushings | Connect HT cables x 2 Transformers | 2 | Lump Sum |
17 | 39121706 | Transformer bushings | Regenerate transformer oil both on 3MVA transformer and tertiary transformer x 2 Transformers | 2 | Lump Sum |
18 | 39121706 | Transformer bushings | Change or fill up mercury in bulchoz relay (where necessary) and perform dry air tests x 2 Transformers | 2 | Lump Sum |
19 | 39121706 | Transformer bushings | Test 3MVA transformer to ZETDC standards – to be done by ZETDC x 2 Transformers | 2 | Lump Sum |
20 | 39121706 | Transformer bushings | Test tertiary transformer to ZETDC standards – to be done by ZETDC x 2 Transformers | 2 | Lump Sum |
21 | 39121706 | Transformer bushings | Clean transformers externally, clean the substation and supply weed killer. x 2 Transformers | 2 | Lump Sum |
22 | 39121706 | Transformer bushings | Paint the transformers x 2 Transformers | 2 | Lump Sum |
23 | 39121706 | Transformer bushings | Commission the transformers x 2 Transformers | 2 | Lump Sum |